1. Inspect refrigerant pressure with manifold gauge set
this is a method in witch the trouble is located by using a manifold gauge set. Read the manifold gauge pressure when the these conditions are established.
Test conditions:
temperature at the air inlet with the switch set at recirc is 30 – 35 °c (86 – 95 °f)
engine running at 1500 rpm
blower speed control switch at ”hi” position
temperature control dial at ”cool” position a/c switch on
During operation, pressure on low pressure side sometimes become a vacuum and sometime normal
Moisture in refrigerating system freezes at expansion valve orifice causing a temporary stop of cycle, however, when it melts, normal state is restored.
Drier in oversaturected state
moisture in refrigerating system freezes at expansion valve orifice and blocks circulation of refrigerant
Replace condenser
remove moisture in cycle by repeatedly evacuating air
supply proper amount of new refrigerant
Insufficient cooling
Symptom
Probable cause
Diagnosis
Corrective actions
Pressure low on both low and high pressure sides
insufficient cooling performance
Gas leakage in refrigeration system
Insufficient refrigerant
refrigerant leaking
Check for gas leakage and repair if necessary
supply proper amount of new refrigerant
if indicated pressure value is close to a 0 when connected to gauge, create the vacuum after inspecting and repairing location of leak
Poor circulation of refrigerant
Symptom
Probable cause
Diagnosis
Corrective actions
Pressure low on both low and high pressure sides
frost on pipe from condenser to unit
Refrigerant flow obstructed by dirt in receiver
Receiver clogged
Replace condenser
Refrigerant does not circulate
Symptom
Probable cause
Diagnosis
Corrective actions
Vacuum indicated on low pressure side, very low pressure indicated on high pressure side
frost or dew seen on piping before and after receiver/ drier or expansion valve
Refrigerant flow obstructed by moisture or dirt in refrigerating system
refrigerant flow obstructed by gas leaked from expansion valve
Refrigerant does not circulate
Check expansion valve
clean out dirt in expansion valve by air blowing
replace condenser
evaporate air and supply proper amount of new refrigerant.
For gas leakage from expansion valve, replace expansion valve
Refrigerant overcharged or insufficient cooling of condenser
Symptom
Probable cause
Diagnosis
Corrective actions
Pressure too high on both low and high pressure sides
Unable to develop sufficient performance due to excessive use of refrigerating system
insufficient cooling of condenser
Excessive refrigerant in cycle"too much refrigerant supplied
condenser cooling insufficient"condenser fins clogged at cooling fan
Clean condenser
check cooling fan with cooling fan motor operation
if (1) and (2) are in normal state, check amount of refrigerant and supply proper amount of refrigerant
Air present in refrigeration system
Symptom
Probable cause
Diagnosis
Corrective actions
Pressure too high on both low and high pressure sides
the low pressure piping too hot to the touch
Air entered in refrigerating system
Air present in refrigerating system
insufficient vacuum purging
Check compressor oil to see if it is see if it is dirty or insufficient
evacuate air and supply new refrigerant
Expansion valve improperly
Symptom
Probable cause
Diagnosis
Corrective actions
Pressure too high on both low and high pressure sides
frost or large amount of dew on piping on low pressure side
Trouble in expansion valve
Excessive refrigerant in low pressure piping
expansion valve opened too wide
Check expansion valve
Defective compression compressor
Symptom
Probable cause
Diagnosis
Corrective actions
Pressure too high on low high pressure sides
pressure too low to on high pressure side
Internal leak in compressor
Compression failure
leakage from valve damaged or broken sliding parts
Repair or replace compressor
Gauge readings (reference)
?