Evaporator temperature sensor inspection
In this manual: Heater and air conditioner systems
~1min read
1. Turn the AUTO switch on.
2. Set the temperature control at MAX COLD (Turn the left).
3. Turn the A/C switch.
4. Set the RECIRCULATE mode.
5. Close all doors and windows.
6. Wait for 5 minutes.7. Remove the glove compartment.

8. Disconnect the evaporator temperature sensor.
9. Measure the temperature at the blower inlet.
10.Measure the resistance between terminals of the evaporator temperature sensor.
- If the resistance is not as shown in the graph, replace the evaporator temperature sensor.