Heater / Air Conditioning

Inspection

~1min read

INSPECTION

PROCEDURE

1. INSPECT COOLER THERMISTOR (CABIN TEMPERATURE SENSOR)

(a) Check the resistance.

(1) Measure the resistance according to the value(s) shown in the table below.

Standard resistance:

Tester Connection

Condition

Specified Condition

1 - 2

10 °C

3.00 to 3.73 kΩ

15 °C

2.45 to 2.88 kΩ

20 °C

1.95 to 2.30 kΩ

25 °C

1.60 to 1.80 kΩ

30 °C

1.28 to 1.47 kΩ

35 °C

1.00 to 1.22 kΩ

40 °C

0.80 to 1.00 kΩ

45 °C

0.65 to 0.85 kΩ

50 °C

0.50 to 0.70 kΩ

55 °C

0.44 to 0.60 kΩ

60 °C

0.36 to 0.50 kΩ

NOTICE:

  • Hold the cooler thermistor (cabin temperature sensor) by its connector only. Touching the sensing portion may change the resistance value.
  • When measuring, the temperature of the cooler thermistor (cabin temperature sensor) must be the same as the ambient temperature.

HINT:

Resistance decreases as temperature increases (see graph).

If the result is not as specified, replace the cooler thermistor (cabin temperature sensor).

*a

Component without wire harness connected

(Cooler Thermistor (Cabin Temperature Sensor))

*b

Sensing Part

*c

Resistance (kΩ)

*d

Temperature (°C (°F))

*e

Allowable Range