Heater / Air Conditioning

Inspection On Vehicle

8steps
~48min
2/5difficulty
Done 0 of 8

INSPECTION ON VEHICLE

PROCEDURE

1. CHECK REFRIGERANT PRESSURE USING MANIFOLD GAUGE SET

HINT:

The following examples show manifold gauge set readings and the corresponding air conditioning system problems.

(a) Read the manifold gauge pressure when the following conditions are met:

  • All doors fully open.
  • Engine running at idle.
  • A/C switch set to ON.
  • Temperature control set to MAX COOL.
  • Fan speed set to HIGH.
  • The intake air temperature with recirculated air selected is 30 to 35 °C.

(1) The air conditioning system operates normally

Gauge Reading

Pressure Side

Refrigerant Amount

Low

150 to 250 kPa (1.5 to 2.5 kgf/cm2, 22 to 36 psi)

High

1,370 to 1,570 kPa (14.0 to 16.0 kgf/cm2, 199 to 228 psi)

*a

LO

*b

HI

(2) The air conditioning system operates abnormally

  1. During operation, the low pressure side fluctuates between normal pressure and vacuum.

    *a

    LO

    *b

    HI

    Symptom

    The air conditioning system cools intermittently and then stops cooling.

    Probable cause

    Moisture in the air conditioning system freezes at the expansion valve orifice, temporarily stopping refrigerant flow.

    After the system is stopped and the temperature rises, the ice melts and normal operation temporarily returns.

    Diagnosis

    Cooler dryer (built into the condenser reservoir) saturated with moisture

    Moisture in the air conditioning system freezes at the expansion valve orifice and stops refrigerant flow.

    Corrective Measures

    Replace the cooler dryer

    Remove moisture by repeatedly evacuating the air conditioning system

    Recharge the air conditioning system with the correct amount of new or purified refrigerant.

    HINT:

    In the example above, moisture is present in the air conditioning system.

  2. Low pressure on both low and high pressure sides

    *a

    LO

    *b

    HI

    Symptom

    The air conditioning system does not cool effectively

    Insufficient cooling performance

    Probable cause

    Refrigerant leaks from the air conditioning system

    Diagnosis

    Insufficient refrigerant amount

    Refrigerant leak

    Corrective Measures

    Check for refrigerant leaks and repair as necessary

    Recharge the air conditioning system with the correct amount of new or purified refrigerant.

    If the gauges indicate a pressure close to 0, evacuate the air conditioning system after the leak has been repaired.

    HINT:

    In the example above, the refrigerant amount is insufficient.

  3. Low pressure on both low and high pressure sides

    *a

    LO

    *b

    HI

    Symptom

    The air conditioning system does not cool effectively

    Frost has formed on the piping connecting the condenser and the evaporator

    Probable cause

    Refrigerant flow is obstructed by debris in the internal tubes of the condenser core.

    Diagnosis

    Condenser clogged

    Corrective Measures

    Replace the condenser

    HINT:

    In the example above, refrigerant circulation is weak.

  4. A vacuum is indicated on the low pressure side and a very low pressure is indicated on the high pressure side

    *a

    LO

    *b

    HI

    Symptom

    The air conditioning system does not cool effectively (the cooling system may cool momentarily)

    Frost or condensation visible on the piping upstream and downstream of the receiver/dryer assembly or the expansion valve

    Probable cause

    Refrigerant flow is restricted by moisture or contaminants in the air conditioning system

    Expansion valve stuck in the closed position

    Diagnosis

    Refrigerant does not circulate

    Corrective Measures

    Replace the expansion valve

    Replace the condenser

    Evacuate the air conditioning system and recharge it with the correct amount of new or purified refrigerant

    HINT:

    In the example above, refrigerant does not circulate.

  5. Excessively high pressure on both low and high pressure sides

    *a

    LO

    *b

    HI

    Symptom

    The air conditioning system does not cool effectively

    Probable cause

    Unable to provide sufficient performance due to excessive refrigerant amount

    Condenser cooling efficiency is insufficient

    Diagnosis

    Excessive amount of refrigerant in the air conditioning system because too much refrigerant was added during recharging

    Condenser cooling efficiency is insufficient because the condenser fins are clogged or the condenser cooling fan is faulty

    Corrective Measures

    Clean the condenser

    Check the operation of the condenser cooling fan

    If the condenser is clean and the fan operates normally, check the refrigerant quantity and recharge the air conditioning system with the correct amount of new or recycled refrigerant

    HINT:

    In the example above, the air conditioning system is overcharged or the condenser cooling efficiency is insufficient.

  6. Excessively high pressure on both low and high pressure sides

    *a

    LO

    *b

    HI

    Symptom

    The air conditioning system does not cool

    Low pressure line too hot to the touch

    Probable cause

    Air in the air conditioning system

    Diagnosis

    Air present in the air conditioning system

    Insufficient vacuum time when evacuating the air conditioning system

    Corrective Measures

    Replace the cooler dryer

    Check the compressor oil: contamination or insufficient quantity

    Evacuate the air conditioning system and recharge it with new or recycled refrigerant.

    NOTICE:

    These gauge readings appear when the air conditioning system has been opened, then recharged without being evacuated.

    HINT:

    In the example above, moisture is present in the air conditioning system.

  7. Excessively high pressure on both low and high pressure sides

    *a

    LO

    *b

    HI

    Symptom

    The air conditioning system does not cool effectively

    Large amount of frost or condensation on the low pressure line

    Probable cause

    The expansion valve may be stuck in the open position or is metering the refrigerant incorrectly

    Diagnosis

    Excess refrigerant in the low pressure line

    Expansion valve opening too large

    Corrective Measures

    Replace the expansion valve

    HINT:

    The example above indicates a malfunction of the expansion valve.

  8. Pressure is too high on both the high and low pressure sides, or pressure is too low on the high pressure side

    *a

    LO

    *b

    HI

    Symptom

    The air conditioning system does not cool effectively

    Probable cause

    Internal leak in the compressor

    Diagnosis

    Low compression

    Leak from a damaged valve or any other compressor component

    Corrective Measures

    Replace the compressor

    HINT:

    The example above indicates insufficient compressor compression.

(3) Gauge readings (reference)

*a

Low pressure side pressure in kPa (kgf/cm2, psi)

*b

High pressure side pressure in kPa (kgf/cm2, psi)

*c

Blower high zone

*d

Blower low zone