Heater / Air Conditioning

Inspection On Vehicle

~4min read

INSPECTION ON VEHICLE

PROCEDURE

1. INSPECT AIR CONDITIONING PRESSURE SENSOR (DENSO make)

(a) Check the wire harness.

(1) Disconnect the A22 connector from the air conditioning pressure sensor.

(2) Disconnect the F71 connector from the air conditioning amplifier assembly.

(3) Measure the resistance according to the value(s) in the table below.

Standard resistance:

Tester Connection

Condition

Specified Condition

A22-1 (-) - F71-2 (SG-2)

Always

Below 1 Ω

A22-2 (PR) - F71-24 (PRE)

Always

Below 1 Ω

A22-3 (+) - F71-6 (S5-3)

Always

Below 1 Ω

A22-1 (-) or F71-2 (SG-2) - Body ground

Always

10 kΩ minimum

A22-2 (PR) or F71-24 (PRE) - Body ground

Always

10 kΩ minimum

A22-2 (PR) or F71-24 (PRE) - Body ground

Always

10 kΩ minimum

If the resistance is not as specified, repair the wire harness.

*a

Component without wire harness connected

(air conditioning pressure sensor)

*b

Component without wire harness connected

(A/C Amplifier Assembly)

(4) Reconnect the F71 connector to the air conditioning amplifier assembly.

(5) Turn the ignition switch to ON.

(6) Measure the voltage according to the value(s) in the table below.

Standard voltage:

Tester Connection

Condition

Specified Condition

A22-3 (+) - Body ground

Ignition Switch in ON position

4,75 à 5,25 V

If the voltage is not as specified, repair the wire harness or replace the air conditioning amplifier assembly.

*a

Component without wire harness connected

(air conditioning pressure sensor)

(b) Inspect the air conditioning pressure sensor.

(1) Connect the connector to the air conditioning pressure sensor.

(2) Install a manifold gauge set.

(3) Turn the A/C switch to ON.

(4) Measure the voltage according to the value(s) specified in the table below.

HINT:

Check the rear of the connector while it is connected to the air conditioning amplifier assembly.

Standard voltage:

Tester Connection

Condition

Specified Condition

F71-24 (PRE) - F71-2 (SG-2)

Refrigerant pressure: Normal pressure (less than 3,025 kPa (30.8 kgf/cm2, 439 psi) and more than 176 kPa (1.8 kgf/cm2, 26 psi))

0,74 à 4,61 V

If the voltage is not as specified, replace the air conditioning pressure sensor.

*a

Component with Wire Harness Connected

(A/C Amplifier Assembly)

2. INSPECT AIR CONDITIONING PRESSURE SENSOR (VALEO make)

(a) Check the wire harness.

(1) Disconnect the A52 connector from the air conditioning pressure sensor.

(2) Disconnect the F72 connector from the air conditioning amplifier assembly.

(3) Measure the resistance according to the value(s) in the table below.

Standard resistance:

Tester Connection

Condition

Specified Condition

A52-3 (-) - F72-32 (SG-2)

Always

Below 1 Ω

A52-2 (PR) - F72-33 (PRE)

Always

Below 1 Ω

A52-1 (+) - F72-34 (S5-3)

Always

Below 1 Ω

A52-1 (+) - Body ground

Always

10 kΩ minimum

A52-2 (PR) - Body ground

Always

10 kΩ minimum

A52-3 (SG-2) - Body ground

Always

10 kΩ minimum

If the resistance is not as specified, repair the wire harness.

*a

Component without wire harness connected

(air conditioning pressure sensor)

*b

Component without wire harness connected

(A/C Amplifier Assembly)

(4) Reconnect the F72 connector to the air conditioning amplifier assembly.

(5) Turn the ignition switch to ON.

(6) Measure the voltage according to the value(s) in the table below.

Standard voltage:

Tester Connection

Condition

Specified Condition

A52-1 (+) - Body ground

Ignition Switch in ON position

4,75 à 5,25 V

If the voltage is not as specified, repair the wire harness or replace the air conditioning amplifier assembly.

*a

Component without wire harness connected

(air conditioning pressure sensor)

(b) Inspect the air conditioning pressure sensor.

(1) Install a manifold gauge set.

(2) Connect the A52 connector to the air conditioning pressure sensor.

(3) Start the engine.

(4) Measure the voltage according to the value(s) specified in the table below.

*a

Component with Wire Harness Connected

(A/C Amplifier Assembly)

-

-

Standard voltage:

Tester Connection

Condition

Specified Condition

F72-33 (PRE) - F72-32 (SG-2)

Refrigerant pressure: Normal pressure (less than 3,025 kPa (30.8 kgf/cm2, 439 psi) and more than 176 kPa (1.8 kgf/cm2, 26 psi))

0,63 à 4,72 V

If the voltage is not as specified, replace the air conditioning pressure sensor.