Heater / Air Conditioning

Pressure Sensor Circuit (B1423)

~9min read

DESCRIPTION

This DTC is stored if the high-pressure side refrigerant pressure is extremely low (195 kPa (2.0 kgf/cm2, 28 psi) maximum) or extremely high (2,812 kPa (28.7 kgf/cm2, 408 psi) minimum). The A/C pressure sensor, installed on the high-pressure side pipe to detect refrigerant pressure, sends a refrigerant pressure signal to the A/C amplifier assembly. The A/C amplifier assembly converts this signal into a pressure value according to the sensor characteristics and uses it to control the compressor.

DTC No.

Detection Item

DTC Detection Condition

Suspected Area

Memory

B1423

Pressure Sensor Circuit

  • Open in Air Conditioning Pressure Sensor Circuit
  • Short in Air Conditioning Pressure Sensor Circuit
  • The refrigerant pressure on the high-pressure side is extremely low (195 kPa (2.0 kgf/cm2, 28 psi) maximum) or extremely high (2,812 kPa (28.7 kgf/cm2, 408 psi) minimum)
  • Air Conditioning Pressure Sensor
  • Harness or connector between the A/C pressure sensor and the A/C amplifier assembly
  • Air Conditioning Amplifier Assembly
  • Cooler expansion valve (stuck, jammed)
  • Cooler condenser assembly (blocked, cooling capacity reduced due to dirt)
  • Cooler receiver drier (moisture in the refrigerant cycle cannot be removed)
  • Cooling fan system (unable to cool the cooler condenser assembly)
  • Air conditioning system (leaks, blockage)

-

Vehicle Operating Conditions

Sequence 1

Sequence 2

Sequence 3

Sequence 4

Diagnostic Condition

Ignition Switch in ON position

○

○

○

○

Malfunction Status

Open in Air Conditioning Pressure Sensor Circuit

○

-

-

-

Short in Air Conditioning Pressure Sensor Circuit

-

○

-

-

The high-pressure side refrigerant pressure is extremely low (195 kPa (2.0 kgf/cm2, 28 psi) maximum)

-

-

○

-

The high-pressure side refrigerant pressure is extremely high (2,812 kPa (28.7 kgf/cm2, 408 psi) minimum)

-

-

-

○

Detection Duration

4 seconds minimum

4 seconds minimum

4 seconds minimum

4 seconds minimum

Number of Trips

1 trip(s)

1 trip(s)

1 trip(s)

1 trip(s)

WIRING DIAGRAM

PRECAUTION / NOTICE / HINT

HINT:

If DTC B1423/23 and B14B8 are output simultaneously, troubleshoot DTC B14B8 first.

Click here

PROCEDURE

  1. CHECK WHETHER DTCs ARE OUTPUT

(a) Check the DTCs.

Click here

Body Electrical > Air Conditioner > Trouble Codes

Result:

Result

Proceed to

DTC B14B8 is output

A

DTC B14B8 is not output

B

A

GO TO DTC B14B8

B
  1. CHECK FOR REFRIGERANT SHORTAGE

(a) Prepare the vehicle as described in the table below.

Measurement condition:

Item

Condition

A/C switch

ON

Ambient temperature*

0 à 49 °C

Blower speed

HI

*: If the ambient temperature is not within the specified range, do not perform this check.

(b) Connect the Techstream to the DLC3.

(c) Turn the ignition switch to ON.

(d) Turn on the Techstream.

(e) Select the following menu items: Body Electrical / Air Conditioner / Utility / Refrigerant Gas Volume Check.

Body Electrical > Air Conditioner > Utility

Refrigerant Gas Volume Check

Result:

Result

Refrigerant level

Refrigerant Shortage

Insufficient quantity or leak

Proper refrigerant

Correct

Result:

Result

Proceed to

Insufficient quantity or leak

A

Correct

B

B

GO TO STEP 4

A
  1. REPAIR A LEAK IN THE AIR CONDITIONING SYSTEM

(a) Identify the source of the refrigerant leak.

Click here

(b) Repair the identified area of the air conditioning system.

(c) Evacuate the air conditioning system.

NEXT

CHARGE THE SYSTEM WITH REFRIGERANT

  1. CHECK REFRIGERANT PRESSURE

(a) Connect the Techstream to the DLC3.

(b) Turn the ignition switch to ON.

(c) Turn on the Techstream.

(d) Select the following menu items: Body Electrical / Air Conditioner / Data List.

(e) Read the Data List by following the instructions on the Techstream.

Body Electrical > Air Conditioner > Data List

Tester display

Item

Range

Normal Condition

Diagnostic Note

Regulator Pressure Sensor

Air Conditioning Pressure Sensor

Min.: -456.6 kPaG

Max.: 3,294.3 kPaG

Actual Refrigerant Pressure Displayed

-

Body Electrical > Air Conditioner > Data List

Regulator Pressure Sensor

(f) Connect a manifold gauge set.

Click here

(g) Read the manifold gauge pressure when the following conditions are met.

(1) Prepare the vehicle as indicated in the table below.

Measurement condition:

Item

Condition

Vehicle Doors

Fully open

Temperature control setting

MAX COLD

Blower speed

HI

A/C switch

ON

Recirculation/Fresh Air Switch

RECIRCULATION

Indoor Temperature

25 à 35 °C

Standard Pressure:

Low Pressure Side

150 to 250 kPa (1.5 to 2.5 kgf/cm2, 22 to 36 psi)

High Pressure Side

1,370 to 1,570 kPa (14 to 16 kgf/cm2, 199 to 228 psi)

(h) Compare the values displayed on the Data List and on the pressure gauge.

OK:

The values displayed on the Data List and on the pressure gauge match.

OK

CHARGE THE SYSTEM WITH REFRIGERANT

NG
  1. CHECK HARNESS AND CONNECTOR (POWER SOURCE CIRCUIT)

(a) Disconnect the air conditioning pressure sensor connector.

*a

Front view of wire harness side connector

(to Air Conditioning Pressure Sensor)

(b) Measure the voltage according to the value(s) in the table below.

Standard voltage:

Tester Connection

Ignition switch position

Specified Condition

A52-3 (+) - A52-1 (-)

Ignition Switch in ON position

4,75 à 5,25 V

NG

GO TO STEP 10

OK
  1. CHECK HARNESS AND CONNECTOR (AIR CONDITIONING PRESSURE SENSOR - BODY GROUND)

(a) Measure the resistance according to the value(s) in the table below.

Standard resistance:

Tester Connection

Condition

Specified Condition

A52-1 (-) - Body ground

Always

Below 1 Ω

NG

GO TO STEP 9

OK
  1. CHECK HARNESS AND CONNECTOR (AIR CONDITIONER AMPLIFIER ASSEMBLY - AIR CONDITIONING PRESSURE SENSOR)

(a) Disconnect the F138 connector from the air conditioner amplifier assembly.

(b) Measure the resistance according to the value(s) in the table below.

Standard resistance:

Tester Connection

Condition

Specified Condition

A52-2 (PR) - F138-24 (PRE)

Always

Below 1 Ω

A52-2 (PR) or F138-24 (PRE) - Body ground

Always

10 kΩ minimum

NG

REPAIR OR REPLACE HARNESS OR CONNECTOR

OK
  1. CHECK AIR CONDITIONING PRESSURE SENSOR (SENSOR SIGNAL CIRCUIT)

(a) Measure the voltage under the following conditions.

Measurement condition:

Item

Condition

Vehicle Doors

Fully open

Temperature control setting

MAX COLD

Blower speed

HI

A/C switch

ON

Recirculation/Fresh Air Switch

RECIRCULATION

Indoor Temperature

25 à 35 °C

NOTICE:

  • If the high pressure side refrigerant pressure becomes extremely high during the check (voltage exceeds 4.61 V), the fail-safe function stops compressor operation. Therefore, measure the voltage before the fail-safe function activates.
  • The voltage must be measured for a certain period (approximately 10 minutes), as the malfunction may reoccur after some time.

HINT:

When the outside temperature is low (below -15 °C), the compressor stops due to the operation of the thermistor assembly and No. 1 cooler thermistor (evaporator temperature sensor) in order to prevent the evaporator from freezing. In this case, perform the check indoors with the vehicle warm.

(1) Measure the voltage according to the value(s) shown in the table below.

Standard voltage:

Tester Connection

Condition

Specified Condition

F138-24 (PRE) - Body ground

Ignition Switch in ON position

(A/C switch: ON)

0,74 à 4,61 V

*a

Component with Wire Harness Connected

(A/C Amplifier Assembly)

(b) Connect the Techstream to the DLC3.

(c) Turn the ignition switch to ON.

(d) Turn on the Techstream.

(e) Select the following menu items: Body Electrical / Air Conditioner / Data List.

(f) Read the Data List by following the Techstream instructions.

Body Electrical > Air Conditioner > Data List

Tester display

Item

Range

Normal Condition

Diagnostic Note

Regulator Pressure Sensor

Air Conditioning Pressure Sensor

Min.: -456.6 kPaG

Max.: 3,294.3 kPaG

Actual Refrigerant Pressure Displayed

-

Body Electrical > Air Conditioner > Data List

Regulator Pressure Sensor

OK:

The voltage and the value displayed on the Data List change.

Result:

Result

Proceed to

OK

A

NG (voltage changes but the value displayed in the Data List does not change.)

NG (voltage does not change).

B

A

REPLACE AIR CONDITIONING AMPLIFIER ASSEMBLY

B

REPLACE AIR CONDITIONING PRESSURE SENSOR

  1. CHECK HARNESS AND CONNECTOR (AIR CONDITIONER AMPLIFIER ASSEMBLY - AIR CONDITIONING PRESSURE SENSOR)

(a) Disconnect the F138 connector from the air conditioner amplifier assembly.

(b) Measure the resistance according to the value(s) in the table below.

Standard resistance:

Tester Connection

Condition

Specified Condition

A52-1 (-) - F138-2 (SG-2)

Always

Below 1 Ω

A52-1 (-) or F138-2 (SG-2) - Body ground

Always

10 kΩ minimum

OK

REPLACE AIR CONDITIONING AMPLIFIER ASSEMBLY

NG

REPAIR OR REPLACE HARNESS OR CONNECTOR

  1. CHECK HARNESS AND CONNECTOR (AIR CONDITIONER AMPLIFIER ASSEMBLY - AIR CONDITIONING PRESSURE SENSOR)

(a) Disconnect the F138 connector from the air conditioner amplifier assembly.

(b) Measure the resistance according to the value(s) in the table below.

Standard resistance:

Tester Connection

Condition

Specified Condition

A52-3 (+) - F138-6 (S5-3)

Always

Below 1 Ω

A52-3 (+) or F138-6 (S5-3) - Body ground

Always

10 kΩ minimum

OK

REPLACE AIR CONDITIONING AMPLIFIER ASSEMBLY

NG

REPAIR OR REPLACE HARNESS OR CONNECTOR